Specifications
Total Area5,000 square feet
Floor to Ceiling Height15 feet
Raised Floor to Ceiling Height12 feet
Raised Floor Height29.5 inches
Raised Floor Loading Capacity1350 Kg / square metre
Power
Power FeedFrom BSES
Transformer Capacity3 * 2000 kVA
Diesel Generator3 * 2000 kVA
UPSN:N,12 * 5000 kVA
Battery Backup15 minutes at full load
Standard Power Per Rack32 A / 16 A
STS3 and 6 kVA at rack level
Security
Entry to Sever HallPunch card
Entry to all Critical AreasProximity readers
CCTV RecordingDVR
Video Storage Recording Duration30 days
24*7 Security GuardsYes
Air Conditioning / Environment
Type RedundancyPrecision AC with N+1 redundancy
Temperature Nominal Set Point20 degrees Celsius
Humidity Nominal Set Point50%
Fire Protection
High Sensitivity Smoke DetectionYes
Fire Alarm SystemAddressable
Type of Suppression SystemNovec
Suppression ModeAutomatic / Manual